Fuse Link Manufacturer & Supplier | Reliable Replacement Fuse Links for Dropout Fuse Cutouts

 

High-voltage expulsion fuse links serve as precision overcurrent protection elements installed inside outdoor drop-out fuse tubes. Upon experiencing persistent overload or short-circuit faults, the fusible element melts instantaneously, triggering an internal arc-extinguishing expulsion process that isolates the faulty line. Standardized for reliable time-current coordination, these fuse links protect distribution transformers and overhead lines from severe electrical damage.

 

 
 
Product Types & Categories
Time-Current Characteristics

Type K (K-Link / Fast): Fast-acting fuse links providing rapid fault clearing for aggressive short-circuit isolation.

Type T (T-Link / Slow): Slow-acting fuse links designed for superior coordination with upstream reclosers and protective relays.

Buttonhead Configurations

Removable Buttonhead: Features a detachable top threaded terminal fitting standard 100A/200A fuse holders.

Solid / Universal Buttonhead: Integrated single-piece terminal head for high mechanical pull-strength applications.

Current Ratings
Available from 1A up to 200A (comprising low-control and high-current distribution series).

 

Technical Specifications

Parameter

Specification Range

Rated Voltage

11kV - 38kV

Rated Current Range

1A - 200A (Type K and Type T)

Tensile Strength

>= 45N (Permanent tension without elongation)

Conductor Materials

High-strength tinned copper, silver-plated copper, or fusible alloy elements

Leader Material

Flexible tinned copper braided wire / stranded copper cable

Operating Temperature

-40 deg C to +85 deg C

Standard Compliance

IEC 60282-2, ANSI/IEEE C37.42, NEMA SG2

 

Applications & Operating Conditions

 
 
01
 

Primary Applications

Internal core element for 10kV to 33kV outdoor drop-out fuse cutouts.
Overcurrent and short-circuit protection for pole-mounted distribution transformers.

 
02
 

Operating Environment

Designed for outdoor hermetically sealed fuse tubes exposed to heavy ambient temperature fluctuations (-40 deg C to +55 deg C).

High humidity and coastal salt-mist environment adaptability through corrosion-resistant lead wires.

 
03
 

Materials & Key Performance

Fusible Element Design: Precision-calibrated dual-material element combining high-conductivity strain wire (tinned copper/silver alloy) with tension-relieved solder joints to ensure exact time-current characteristic curves.

Tensile Strength & Crimping: Mechanically swaged terminal crimps withstand high pre-tension forces from upper cutout contact springs, preventing premature mechanical fatigue or wire snapping prior to actual fault conditions.

Arc Quenching Contribution: Paired with internal fuse tube liners to instantly vaporize and generate high-pressure deionizing gas when fault currents pass through the melting section.

Fuse Link Type K

 

Manufacturing & Quality Control

 

1

Calibration & Resistance Testing

 

Automated micro-ohm resistance sorting benches verify that every fuse link matches strict electrical resistance thresholds before packaging.

2

Tensile Proof Testing

 

100% mechanical pull-force testing applied to ensure leader-to-element joints exceed minimum operational load specifications.

3

Time-Current Characteristic (TCC) Verification

Sample-batch destructive testing performed in high-current laboratories to validate melting time curves against IEC/IEEE standards.

4

Anti-Oxidation Treatment

 

Tinned and silver-coated copper leads undergo anti-corrosion passivation baths to prevent surface darkening during long-term warehouse storage.

 

Customization & OEM/ODM

Leader Length Variations

Customizable flexible leader lengths and stripped wire ends tailored to non-standard or oversized cutout tube dimensions.

Special Ampere Ratings

Tailored low-ampere or non-standard intermediate rating calibration (e.g., fractional amp ratings) for specialized utility requirements.

Packaging & Labeling

Customized barcoded box labeling, individual polybag separation, and utility-specific part number printing.

 

Packaging & Delivery

 

 
 

Packaging Structure

Packed in moisture-resistant individual paper sleeves or anti-static sealed polyethylene bags, bundled in sturdy corrugated cartons with protective foam dividers to prevent physical tangling or bending of flexible leads.

 
 
 

Moisture Barrier

Desiccant packs included inside master cartons to prevent oxidation and moisture absorption during maritime transit.

 
 
 

Lead Time

10 - 20 days for standard volume orders; immediate stock dispatch available for regular rating series.

 

 

 

ISO Certificates

productcate-353-500
productcate-353-500
productcate-1-1
productcate-353-500

 

 

FAQ

 

Q: What is the primary difference between Type K and Type T fuse links?

A: Type K (fast) links have a speed ratio between 6 and 8, clearing faults rapidly to protect equipment. Type T (slow) links have a speed ratio between 10 and 13, designed for selective coordination with upstream reclosers to avoid unnecessary neighborhood outages.

Q: Are your fuse links compatible with standard ANSI and IEC cutout tubes?

A: Yes. Our fuse links are dimensionally engineered to fit standard universal IEC 60282-2 and ANSI/IEEE C37.42 drop-out fuse tubes.

Q: How do you ensure the precision of the time-current melting curve?

A: We utilize high-precision automated resistance sorting equipment and strict alloy composition controls during production, followed by sample batch testing in professional current laboratories.

Q: What is the tensile strength of the fuse link leader and element?

A: The mechanical pull strength is rated at 45 Newtons minimum, ensuring the link withstands the heavy mechanical tension exerted by the upper contact spring of the fuse cutout without premature stretching.

Q: What packaging methods are used to prevent tangling during shipping?

A: Each fuse link is individually enclosed in a protective paper sleeve or independent polybag and organized in partitioned cartons, preventing the flexible braided leads from tangling.

Q: What is the standard Minimum Order Quantity (MOQ) for custom lead lengths or ratings?

A: The MOQ for customized leader lengths or non-standard amp ratings starts at 1,000 units per specification, supporting flexible utility project staging.

 

modular-1
Request a Quote

To receive a technical proposal, time-current characteristic curves, or commercial quotation for your fuse link requirements, please provide:
Rated Amperage & Characteristic Type (Type K / Type T)
Buttonhead Style (Removable / Solid)
Required Standards (IEC / IEEE) & Order Quantity
Contact our engineering sales team directly at sale@gao-dian.com.

 

Gaodian Technology Co., Ltd. is one of the most experienced fuse link manufacturers and suppliers in China. We warmly welcome you to buy customized fuse link made in China here from our factory. If you have any enquiry about cooperation, please feel free to email us.

fuse link, Fuse Link Type K, Fuse Link Type T